104C Version 3 ♦ ProLinx Gateway
Configuring the Gateway
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 21 of 139
August 4, 2011
Pass-Through Events
This parameter specifies if spontaneous event messages received from the
servers will be passed to the mailbox interface. If the parameter is set to N,
event messages will not be passed to the mailbox interface. If the parameter is
set to Y, the driver will pass all events received to the mailbox interface using
mailbox identifier 9903 & -9903. The Mailbox Interface should be enabled by
setting a valid value for "Mailbox Offset" if this feature is utilized.
2.1.3 [IEC-60870-5-104 Client x]
Server IP Address
IP address of the remote server that will be connected to this client
Sector Count - 1 to 2
1 to 2
This parameter sets the number of Sectors (separate databases or Multiple
Application Layer ASDU addresses) contained in this Session (controlled
device). This version of the application supports 1 to 2 sectors for each
Client/session.