Reference

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 120 of 139

ProSoft Technology, Inc.

August 4, 2011

Process information in control direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)

<45> := Single command

C_SC_NA_1

<46> := Double command

C_DC_NA_1

<47> := Regulating step command

C_RC_NA_1

<48> := Set point command, normalized value

C_SE_NA_1

<49> := Set point command, scaled value

C_SE_NB_1

<50> := Set point command, short floating point value

C_SE_NC_1

<51> := Bitstring of 32 bit

C_BO_NA_1

<58> := Single command with time tag CP56Time2a

C_SC_TA_1

<59> := Double command with time tag CP56Time2A

C_DC_TA_1

<60> := Regulating step command with time tag CP56Time2A

C_RC_TA_1

<61> := Set point command, normalized value with time tag

CP56Time2A C_SE_TA_1

<62> := Set point command, scaled value with time tag CP56Time2A

C_SE_TB_1

<63> := Set point command, short float value with time tag

CP56Time2A C_SE_TC_1

<64> := Bitstring of 32 bit with time tag CP56Time2A

C_BO_TA_1

Either the ASDUs of the set <45>-<51> or of the set <58>-<64> are used.

System information in monitor direction
(Station-specific parameter, mark "X" if used)

<70> := End of initialization

M_EI_NA_1

System information in control direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)

<100> := Interrogation command

C_IC_NA_1

<101> := Counter interrogation command

C_CI_NA_1

<102> := Read command

C_RD_NA_1

<103> := Clock synchronization command

C_CS_NA_1

<105> := Reset process command

C_RP_NC_1

<107> := Test command with time tag CP56Time2a

C_TS_TA_1