beautypg.com

ProSoft Technology 5201-DFNT-104C User Manual

Page 24

background image

Configuring the Gateway

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 24 of 139

ProSoft Technology, Inc.

August 4, 2011

2.1.4 [IEC-60870-5-104 Client x Sector x] Parameters

Common ASDU Address
At the application level, the gateway is identified by the Common ASDU
(Application Service Data Unit) Address
. This address must match the CASDU
sent at the server unit. An ASDU is a data unit that transfers information objects
between the Client and the server.
If the gateway sends a message to a different Common ASDU, the server should
ignore the command.

Online Time Sync
Yes or No
This parameter specifies if the sector in the server device will be sent a time
synchronization command when the server device is first recognized as being
online. This should only be used for devices that do not send an EOI message
after initializing.

Online General Int
Yes or No
This parameter specifies if the sector in the server will be sent a general
interrogation command when the unit is first recognized as being online.