Port physical and protocol specifications, 104 slave port specifications, Driver protocol specifications – ProSoft Technology 5205-104S-PDPS User Manual
Page 93

Reference 4205/5205-TS-104S-PDPS
♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 93 of 128
July 12, 2007
Specification Description
Dimensions
Standard: 5.20H x 2.07W x 4.52D in. (13.2cmH x 5.25cmW x 11.48cmD)
Extended: 5.20H x 2.73W x 4.52D in. (13.2cmH x 6.934cmW x 11.48cmD)
LED Indicators
Power and Module Status
Application Status
Serial Port Activity LED
Serial Activity and Error LED Status
Configuration Serial Port
DB-9M RS-232 only
No hardware handshaking
Ethernet Port (Ethernet modules
only)
RJ45 Connector
Link and Activity LED indicators
Application Serial Ports
RS-232/422/485
RS-232 handshaking configurable
RS-422/485 screw termination included
Serial Port Isolation
2500V RMS port signal isolation per UL 1577
3000V DC min. port to ground and port to logic power isolation
Shipped with Each Unit
Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)
4.1.4
Port Physical and Protocol Specifications
104 Slave Port Specifications
The 104S module acts as a gateway between the IEC-870-5-104, other protocols
and networks, as well as several proprietary interfaces. A 4000-word register
space in the module exchanges data between the two protocols.
General specifications include:
Support for the storage and transfer of up to 4000 registers between
protocols
User-definable module memory usage
Storage of IEC time used in module is available in the database
Configuration via a user-generated text file (downloadable to the module)
Protocol implementation conforms to the IEC-870-5-104 specification with
fully configurable parameters
Priority
Queues
Invalid Bit Monitoring
Supports Redundant Connection
Driver Protocol Specifications
General Parameters
Internal Database
4000 registers (words) available
Communication parameters
Port 0: Baud Rate = 110 to 38.4K baud
Port 1,2,3: Baud Rate = 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd
RTS Timing Delays: 0 to 65535 milliseconds