Information object address, Cause of transmission, Length of apdu – ProSoft Technology 5205-104S-PDPS User Manual
Page 108: Selection of standard asdus, Process information in monitor direction

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Reference
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 108 of 128
ProSoft Technology, Inc.
July 12, 2007
Information object address
(System-specific parameter)
One octet
Structured
Two octets
Unstructured
⌧
Three octets
Cause of transmission
(System-specific parameter)
One octet ⌧ Two octets (with originator address)
Length of APDU
(System-specific parameter, specify the maximum length of the APDU per
system)
The Maximum length of the APDU is 2
46 (default). The maximum length may be
reduced by the system.
2
46 Maximum length of APDU per system
4.8.3
Selection of standard ASDUs
Process information in monitor direction
(Station-specific parameter, mark each Type ID 'X' if it is only used in the
standard direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)
⌧
<1>
:= Single-point information
M_SP_NA_1
⌧
<3>
:= Double-point information
M_DP_NA_1
⌧
<5>
:= Step position information
M_ST_NA_1
<7>
:= Bitstring of 32 bit
M_BO_NA_1
⌧
<9>
:= Measured value, normalized value
M_ME_NA_1
⌧
<11> := Measured value, scaled value
M_ME_NB_1
⌧
<13> := Measured value, short floating point value
M_ME_NC_I
⌧
<15> := Integrated totals
M_IT_NA_1
<20> := Packed single-point information with status change detection
M_PS_NA_1
<21> := Measured value, normalized value without quality descriptor
M_ME_ND_1
⌧
<30> := Single-point information with time tag CP56Time2a
M_SP_TB_1
⌧
<31> := Double-point information with time tag CP56Time2A
M_DP_TB_1