Common Address of ASDU
Common Address of ASDU : 1 #Range 0 to 65535
This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.
Cyclic Data Transmission
Cyclic data transmission : 20000 #Numb of milliseconds between cyclic
#updates
This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permit update times of 1 millisecond to 5
minutes. If the parameter is set to 0, cyclic data reporting will be disabled.
Select/Operate Timeout
Select/Operate Timeout : 10000 #Milliseconds before select timeout
This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. The range of values for
this parameter permit times of 1 millisecond to 30 seconds. If the parameter is
set to 0, the feature will be disabled.
Use ACTTERM with Setpoint
Use ACTTERM with setpoint : 0 #1=Yes, 0=No ACTCON is last response
#to cmd
This parameter determines if an ACTTERM will be sent. If the parameter is set to
Y, then setpoint commands will issue an ACTTERM when the command is
complete. If the parameter is set to N, ACTCON is the last response to a setpoint
command.
Use ACTTERM with Step
Use ACTTERM with step : 1 #1=Yes, 0=No ACTCON is last response
#to cmd
This parameter determines if an ACTTERM will be sent. If the parameter is set to
Y, then step commands will issue an ACTTERM when the command is complete.
If the parameter is set to N, ACTCON is the last response to a step command.
Time DB Offset
Time DB Offset : 3000 #DB location of IEC time
This parameter sets the location in the database where the module's current date
and time will be copied to.