Customizing the Sample Configuration File

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 17 of 128

July 12, 2007

Common Address of ASDU

Common Address of ASDU : 1 #Range 0 to 65535

This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.

Cyclic Data Transmission

Cyclic data transmission : 20000 #Numb of milliseconds between cyclic

#updates

This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permit update times of 1 millisecond to 5
minutes. If the parameter is set to 0, cyclic data reporting will be disabled.

Select/Operate Timeout

Select/Operate Timeout : 10000 #Milliseconds before select timeout

This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. The range of values for
this parameter permit times of 1 millisecond to 30 seconds. If the parameter is
set to 0, the feature will be disabled.

Use ACTTERM with Setpoint

Use ACTTERM with setpoint : 0 #1=Yes, 0=No ACTCON is last response

#to cmd

This parameter determines if an ACTTERM will be sent. If the parameter is set to
Y, then setpoint commands will issue an ACTTERM when the command is
complete. If the parameter is set to N, ACTCON is the last response to a setpoint
command.

Use ACTTERM with Step

Use ACTTERM with step : 1 #1=Yes, 0=No ACTCON is last response

#to cmd

This parameter determines if an ACTTERM will be sent. If the parameter is set to
Y, then step commands will issue an ACTTERM when the command is complete.
If the parameter is set to N, ACTCON is the last response to a step command.

Time DB Offset

Time DB Offset : 3000 #DB location of IEC time

This parameter sets the location in the database where the module's current date
and time will be copied to.