Protocol Implementation
4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 55 of 128
July 12, 2007
[M_ME_NB_1 104]
#
# Default
# Point # DB Address Group(s) Deadband IV DB Bit
# ------- ---------- -------- -------- ---------
START
500 20 00000002 100 # P1 inboard bearing temp
501 21 00000002 100 # P1 outboard bearing temp
502 22 00000002 100 # P1 winding Temp
503 23 00000002 100 # P1 current
504 24 00000002 100 # P2 inboard bearing temp
505 25 00000002 100 # P2 outboard bearing temp
506 26 00000002 100 # P2 winding Temp
507 27 00000002 100 # P2 current
508 28 00000002 100 #
509 29 00000002 100 #
END
[M_ME_NC_1 104]
#
# Default
# Point # DB Address Group(s) Deadband IV DB Bit
# ------- ---------- -------- -------- ---------
START
600 30 00000002 100 #
601 32 00000002 100 #
602 34 00000002 100 #
603 36 00000002 100 #
604 38 00000002 100 #
605 40 00000002 100 #
606 42 00000002 100 #
607 44 00000002 100 #
608 46 00000002 100 #
609 48 00000002 100 #
END
And the parameter points are configured as follows:
M_ME_NA Parameter Offset : 2000 #M_ME_NA IOA offset for parameter data
M_ME_NB Parameter Offset : 2000 #M_ME_NB IOA offset for parameter data
M_ME_NC Parameter Offset : 2000 #M_ME_NC IOA offset for parameter data
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
400 2400
401 2401
402 2402
403 2403
404 2404