[IEC-870-5-104 IP Addresses]
This section enters the IP addresses for the hosts to connect to this unit. The unit
will only accept connections from hosts listed here. This list may contain up to 10
entries between the START and END labels. The address must start in column 1,
and must be entered in standard dot notation.
The following is an example of the [IEC-870-5-104 IP Addresses] section:
[IEC-870-5-104 IP ADDRESSES]
START
192.168.0.207
192.168.0.203
192.168.0.61
END
1.1.8 [IEC-870-5-104
Database]
This section describes the [IEC-870-5-104 Database] section.
Each parameter is described below. Edit the configuration file according to the
needs of your application.
Short Pulse Time
Short Pulse Time : 2000 #MSec for short pulse command
This parameter defines the number of milliseconds to be associated with a short
pulse command. The valid range of numbers for this parameter are 0 to
2,147,483,647. Range is 0 to 2^31-1.
Long Pulse Time
Long Pulse Time : 10000 #MSec for long pulse command
This parameter defines the number of milliseconds to be associated with a long
pulse command. The valid range of numbers for this parameter are 0 to
2,147,483,647. Range is 0 to 2^31–1
M_SP_NA Point Count
M_SP_NA point count : 10 #Number of monitored single-points
This parameter specifies the number of point values assigned in monitored
single-point database. Range is 0 to 1000.
M_DP_NA Point Count
M_DP_NA point count : 10 #Number of monitored dual-points
This parameter specifies the number of point values assigned in monitored dual-
point database. Rang is 0 to 1000.
M_ST_NA Point Count
M_ST_NA point count : 10 #Number of monitored step-points
This parameter specifies the number of point values assigned in monitored step-
point database. Range is 0 to 1000.