Event scan delay, M_sp_na scan events, M_sp_na time type – ProSoft Technology 5205-104S-PDPS User Manual
Page 20: M_dp_na scan events, M_dp_na time type, M_st_na scan events

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Customizing the Sample Configuration File
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 20 of 128
ProSoft Technology, Inc.
July 12, 2007
processor can determine the individual IV quality bit status of each point you
configured.
To disable this feature, set the IV Fail Count parameter to 0. If used, the Cyclic
Set IV Time parameter must be at least 3 times larger than the IV Check Delay
Time.
Event Scan Delay
Event Scan delay : 1 #MSec between event scanning (0-65535)
#0=Disable
If set to 0, the feature will be disabled and the module will not generate any
events. If set from 1 to 65535, the parameter represents the number of
milliseconds between event scanning. This parameter defines how often the
program will scan for new events in the databases.
M_SP_NA Scan Events
M_SP_NA Scan Events : 1 #0=No scanning, 1=scan for events
Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.
M_SP_NA Time Type
M_SP_NA Time Type : 2 #0=None, 2=CP56 time
This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.
M_DP_NA Scan Events
M_DP_NA Scan Events : 1 #0=No scanning, 1=scan for events
Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.
M_DP_NA Time Type
M_DP_NA Time Type : 2 #0=None, 2=CP56 time
This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.
M_ST_NA Scan Events
M_ST_NA Scan Events : 1 #0=No scanning, 1=scan for events
Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.