Process information in control direction – ProSoft Technology 5205-104S-PDPS User Manual
Page 109

Reference 4205/5205-TS-104S-PDPS
♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 109 of 128
July 12, 2007
⌧
<32> := Step position information with time tag CP56Time2A
M_ST_TB_1
<33> := Bitstring of 32 bit with time tag CP56Time2A
M_BO_TB_1
⌧
<34> := Measured value, normalized value with time tag CP56Time2A
M_ME_TD_1
⌧
<35> := Measured value, scaled value with time tag CP56Time2A
M_ME_TE_1
⌧
<36> := Measured value, short floating point value with time tag
CP56Time2A M_ME_TF_1
⌧
<37> := Integrated totals with time tag CP56Time2A
M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2A
M_EP_TD_1
<39> := Packed start events of protection equipment with time tag
CP56time2A M_EP_TE_1
<40> := Packed output circuit information of protection equipment with
time tag CP56Time2a M_EP_TF_1
Process information in control direction
(Station-specific parameter, mark each Type ID 'X' if it is only used in the
standard direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)
⌧
<45>
:=
Single
command
C_SC_NA_1
⌧
<46>
:=
Double
command
C_DC_NA_1
⌧
<47> := Regulating step command
C_RC_NA_1
⌧
<48> := Set point command, normalized value
C_SE_NA_1
⌧
<49> := Set point command, scaled value
C_SE_NB_1
⌧
<50> := Set point command, short floating point value
C_SE_NC_1
<51> := Bitstring of 32 bit
C_BO_NA_1
⌧
<58> := Single command with time tag CP56Time2a
C_SC_TA_1
⌧
<59> := Double command with time tag CP56Time2A
C_DC_TA_1
⌧
<60> := Regulating step command with time tag CP56Time2A
C_RC_TA_1
⌧
<61> := Set point command, normalized value with time tag
CP56Time2A C_SE_TA_1
⌧
<62> := Set point command, scaled value with time tag CP56Time2A
C_SE_TB_1
⌧
<63> := Set point command, short float value with time tag
CP56Time2A C_SE_TC_1