ProSoft Technology 5205-104S-PDPS User Manual
Page 100

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Reference
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 100 of 128
ProSoft Technology, Inc.
July 12, 2007
Status Register Name
Description
10204
Sequence Error Count
This word contains the number of sequence errors
recognized by the module. When the send
sequence number received by the module does not
match the expected sequence number, the
connection is closed and this counter is
incremented.
10205
Bad Address Error Count This word contains the number of messages
received from the remote host that do not contain a
valid common ASDU address in the packet.
10206
Length Error Count
This word contains the number of messages
received from the remote host that do not have a
valid length field.
10207
Receive Frame Count
This word contains the number of message frames
(not packets) received from the host. A packet may
contain more than one message.
10208
Transmit Frame Count
This word contains the number of message frames
sent to the host from the unit.
10209
Socket State Value
(socket 0)
This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for connection
1 = Transmit message if ready
2 = Receive packet and process message
3 = Process multiple messages in packet
50 = Send TestFr Act
51 = Wait for TestFr Con
60 = Send sequence (S-Format) message
1000 = Close Socket
1001 = Wait for socket to close
10210
Socket Open Count
(socket 0)
This word contains the number of times the socket
listen function executed.
10211
Socket Close Count
(socket 0)
This word contains the number of times an active
close function executed.
10212
Socket Connect Count
(socket 0)
This word contains the number of times a
connection was established with the remote host
unit.
10213
…
10222
Host IP Address
(socket 0)
IP address of the client connected to the server.