Use ip list, Override startdt – ProSoft Technology 5205-104S-PDPS User Manual
Page 15

Customizing the Sample Configuration File
4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 15 of 128
July 12, 2007
M_ME_NC Priority : 2 #Unique index for this data type in queue
#(0-5)
M_IT_NA Priority : 6 #Unique index for this data type in queue
#(0-5)
# This section is used to define the parameters utilized for the Invalid Bit
# Monitoring. If this feature is not used, set the parameters to zero. If used,
# the Cyclic Set IV Time must be at least 3 times larger than the IV Check Delay
# Time. If the IV Fail Count parameter is zero, the feature will be disabled.
Cyclic Set IV Time : 60 #Number of sec intervals between IV sets
IV Check Delay Time : 15 #Number of sec intervals between investigation
IV Fail Count : 3 #Number of IV failures recognized before
#reporting
# Event configuration
Event Scan delay : 1 #MSec between event scanning (0-65535) 0=Disable
M_SP_NA Scan Events : 1 #0=No scanning, 1=scan for events
M_SP_NA Time Type : 2 #0=None, 2=CP56 time
M_DP_NA Scan Events : 1 #0=No scanning, 1=scan for events
M_DP_NA Time Type : 2 #0=None, 2=CP56 time
M_ST_NA Scan Events : 1 #0=No scanning, 1=scan for events
M_ST_NA Time Type : 2 #0=None, 2=CP56 time
M_ME_NA Scan Events : 1 #0=No scanning, 1=scan for events
M_ME_NA Time Type : 2 #0=None, 2=CP56 time
M_ME_NB Scan Events : 1 #0=No scanning, 1=scan for events
M_ME_NB Time Type : 2 #0=None, 2=CP56 time
M_ME_NC Scan Events : 0 #0=No scanning, 1=scan for events
M_ME_NC Time Type : 2 #0=None, 2=CP56 time
M_IT_NA Time Type : 2 #0=None, 2=CP56 time
Modify each parameter based on the needs of your application.
Use IP List
Use IP List : 0 #Use IP list to validate connection
#(0=No, 1=Yes)
This parameter specifies if the IP address of the host connected to the system
will be validated. If the parameter is set to 0, any host may connect to the unit. If
the parameter is set to 1, only hosts in the IP list will be permitted to connect to
the unit.
Override StartDT
Override StartDT : 1 #Used to ignore STARTDT/STOPDT state
#(0=No, 1=Yes)
This parameter is used when testing the unit with a simulator or with a client unit
that does not meet the IEC 60870-5-104 specification. After the host connects to
the system, it will send a STARTDT.ACT U-format message to the unit to permit
the unit to start sending data. If the client does not support this requirement, set
the parameter to a value of 1. Set the parameter to 0 if the unit sends the
STARTDT.ACT message.