ProSoft Technology 5205-104S-PDPS User Manual
Page 11

Customizing the Sample Configuration File
4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 11 of 128
July 12, 2007
Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.
Byte Bit
Position
Designation
7 6 5 4 3 2 1 0
0 Lock
Reg
Unio
Req
Sync
Req
Free
Req
WD
on
Res Res Res Station
status
1
WD_Fact_1
2
WD_Fact_2
3
MinTSDR
4
Ident_Number_High
5
Ident_Number_Low
6
Group_Ident
7
Spec_User_Prm_Byte
8 to 243
User_Prm_Data
Byte 7
Spec_User_Prm_Byte
Bit Name
Significance
Default
State
0
Dis_Startbit
The start bit monitoring in the receiver
is switched off with this bit
Dis_Startbit = 1,
That is, start bit monitoring is switched off.
1
Dis_Stopbit
Stop bit monitoring in the receiver is
switched off with this bit
Dis_Stopbit = 0
That is, stop bit monitoring is not switched
off.
2
WD_Base
This bit specifies the time base used
to clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms
WD_Base = 0
That is, the time base is 10 ms.
3 to 4
Res
To be parameterized with 0
0
5
Publisher_Enable
DXB-publisher-functionality of the
SPC3 is activated with this bit
Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegramme are processed
6 to 7
Res
To be parameterized with 0
0