M_me_na point count, M_me_nb point count, M_me_nc point count – ProSoft Technology 5205-104S-PDPS User Manual
Page 23: M_it_na point count, C_sc_na point count, C_dc_na point count, C_rc_na point count, C_se_na point count, C_se_nb point count

Customizing the Sample Configuration File
4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 23 of 128
July 12, 2007
M_ME_NA Point Count
M_ME_NA point count : 10 #Number of monitored normalized-points
This parameter specifies the number of point values assigned in monitored
normalized-point database. Range is 0 to 1000.
M_ME_NB Point Count
M_ME_NB point count : 10 #Number of monitored scaled-points
This parameter specifies the number of point values assigned in monitored
scaled-point database. Range is 0 to 1000.
M_ME_NC Point Count
M_ME_NC point count : 10 #Number of monitored scaled-points
This parameter specifies the number of point values assigned in monitored
scaled short-float point database. Range is 0 to 50.
M_IT_NA Point Count
M_IT_NA point count : 10 #Number of monitored counter-points
This parameter specifies the number of point values assigned in monitored
counter-point database. Range is 0 to 1000.
C_SC_NA Point Count
C_SC_NA point count : 10 #Number of command single-points
This parameter specifies the number of point values assigned in command
single-point database. Range is 0 to 1000.
C_DC_NA Point Count
C_DC_NA point count : 10 #Number of command dual-points
This parameter specifies the number of point values assigned in command dual-
point database. Range is 0 to 1000.
C_RC_NA Point Count
C_RC_NA point count : 10 #Number of command step-points
This parameter specifies the number of point values assigned in command step-
point database. Range is 0 to 1000.
C_SE_NA Point Count
C_SE_NA point count : 10 #Number of command normalized-points
This parameter specifies the number of point values assigned in command
normalized-point database. Range is 0 to 1000.
C_SE_NB Point Count
C_SE_NB point count : 10 #Number of command scaled-points
This parameter specifies the number of point values assigned in command
scaled-point database. Range is 0 to 1000.