Example response block from gw, Example event data block from plc, Example set time data block from plc – ProSoft Technology 5205-104S-PDPS User Manual
Page 64

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Protocol Implementation
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 64 of 128
ProSoft Technology, Inc.
July 12, 2007
Example Response Block From GW
Start Byte
End Byte
Description
0
0
160 (Raw data read)
1
1
150 (Raw data write)
2
3
Start register in database for read
4
5
Number of registers to read (1 to 96)
6
197
Words read from the database
198 198
Reserved
199
199
160 (Raw data read)
Example Event Data Block From PLC
Start Byte
End Byte
Description
0
0
100 (Event data)
1
1
201 (Get Time)
2 3
Event
Count
4 195
Event
Data
196
198
Reserved for future use
199
199
100 (Event data)
Example Response Block From GW
Start Byte
End Byte
Description
0
0
201 (Get Time)
1
1
100 (Event data)
2 3
Year
4 5
Month
6 7
Day
8 9
Hour
10 11
Minutes
12
13
Seconds & milliseconds
14
198
Reserved for future use
199
199
201 (Get Time)
Example Set Time Data Block From PLC
Start Byte
End Byte
Description
0
0
200 (Set Time)
1
1
201 (Get Time)
2 3
Year
4 5
Month
6 7
Day
8 9
Hour
10 11
Minutes
12
13
Seconds & milliseconds
14
198
Reserved for future use
199
199
200 (Set Time)