4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Reference
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 112 of 128
ProSoft Technology, Inc.
July 12, 2007
4.8.5
Basic Application Functions
Station initialization
(Station-specific parameter, mark 'X' if function is used)
⌧
Remote
initialization
Cyclic data transmission
(Station-specific parameter, mark 'X' if function is only used in the standard
direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)
⌧
Cyclic data transmission
Read procedure
(Station-specific parameter, mark 'X' if function is only used in the standard
direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)
⌧
Read
procedure
Spontaneous transmission
(Station-specific parameter, mark 'X' if function is only used in the standard
direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)
⌧
Spontaneous
transmission
Double transmission of information objects with cause of transmission
spontaneous
(Station-specific parameter, mark each information type 'X' where both a Type ID
without time and corresponding Type ID with time are issued in response to a
single spontaneous change of a monitored object)
The following type identifications may be transmitted in succession caused by a
single status change of an information object. The particular information object
addresses for which double transmission is enabled are defined in a project-
specific list.
Single-point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and
M_PS_NA_1
Double-point information M_DP_NA_1, MDP_TA_1 and M_DP_TB_1
Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1
Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1
and M_ME_TD_1
Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and
M_ME_TF_1