Module state – word 10310 byte 0, Last global command – word 10310 byte 1 – ProSoft Technology 5205-104S-PDPS User Manual
Page 69

Protocol Implementation
4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
ProSoft Technology, Inc.
Page 69 of 128
July 12, 2007
Baud rate:
The baud rates SPC3 found
Bits
8 - 11
0000 = 12 Mbaud
0001 = 6 Mbaud
0010 = 3 Mbaud
0011 = 1.5 Mbaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible
SPC3-Release:
Release no. for SPC3
Bits
12 - 15
0000 = Release 0
Rest = Not possible
Further explanation of Status Register [0] – Word 10309 Bit states
Bit 0
Offline/Passive-idle
0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
go offline.
1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
are started.
Bit 4, 5
10 = Data Exchange State is Normal. The SPC3 has a correct configuration.
Module State – Word 10310 Byte 0
Indicates the current state of the module.
0 = Normal Operation
1 = Shutdown
2 = File Transfer
3 = SPC3 ASIC problem
4 = Not in data exchange
Last Global Command – Word 10310 Byte 1
The value of the last global command code received from the master.
Bit
Designation
Significance
0
Reserved
1
Clear_Data
With this command the ASCI output data is deleted in data
transfer buffer and is changed to next transfer data buffer
contents.
2
Unfreeze
With 'Unfreeze' - freezing input data is cancelled.
3
Freeze
The ASCI input data is fetched from next transfer buffer to data
transfer buffer and frozen. New input data is not fetched again
until the master sends the next 'Freeze' command.