4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Diagnostics and Troubleshooting

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 86 of 128

ProSoft Technology, Inc.

July 12, 2007

Viewing PROFIBUS Status

Enable State

Indicates the initialized state of the 4205/5205-TS-104S-PDPS module.

0 = Module is not initialized
1 = Module is initialized

Module State

Indicates the current state of the 4205/5205-TS-104S-PDPS module.

0 = Normal Operation
1 = Shutdown
2 = File Transfer
3 = SPC3 ASIC problem
4 = Not in data exchange

Status Register [0]

SPC3 ASIC slave status information provided to the master.

Offline/Passive-Idle
Offline-/Passive-Idle state

Bit 0

0 = SPC3 is in offline
1 = SPC3 in passive idle

FDL_IND_ST (Fieldbus Data link Layer)
FDL indication is temporarily buffered.

Bit 1

0 = No FDL indication is temporarily buffered.
1 = FDL indication is temporarily buffered.

Diag_Flag
Status diagnostics buffer

Bit 2

0 = The DP master fetches the diagnostics buffer.
1 = The DP master has not yet fetched the diagnostics buffer.

RAM Access Violation
Memory access > 1.5kByte

Bit 3

0 = No address violation
1 = For addresses > 1536 bytes, 1024 is subtracted from the current address, and
there is access to this new address.