beautypg.com

MCZ Athos HYDRO 14 kW User Manual

Page 14

background image

PELLET STOVES

Chapter 2

INSTALLATION AND USE MANUAL

page

14

Theoretical notions for installation

Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited

2.3. PRECAUTIONS

IMPORTANT!
Installation and assembly of the stove must be

carried out by qualified personnel.

The stove must be installed in a suitable position to allow the normal

operations of opening and ordinary maintenance.
The site must be:

capable of providing the environmental conditions for operation

equipped with power supply 230V 50 Hz (EN73-23)

capable of taking an adequate system for smoke discharge

provided with external ventilation

provided with an earth connection complying with CEI 64-8

The stove must be connected to a flue pipe or an internal or

external vertical duct conforming to current standards UNI

7129 - 7131 9615.
The stove must be positioned in such a way that the electrical

plug is accessible.

IMPORTANT!
The stove must be connected to a flue pipe or a

vertical duct which can discharge the fumes at the

highest point of the building.
The fumes are however derived from the combustion

of wood products, and if they come into contact with

or close to walls, they can make dirty marks.
Also take care because the fumes are very hot but

almost invisible, and can cause burns on contact.
The holes for the passage of the smoke pipe and for

the intake of air from outside should be made before

positioning the stove unit.

2.4. CONNECTION TO THE EXTERNAL AIR INTAKE

It is essential that at least as much air must be able to flow into the

room where the stove is installed as is required for proper combustion

in the appliance and for the ventilation of the room. This can be

effected by means of permanent openings in the walls of the room to

be ventilated, which give onto the outside, or by single or collective

ventilation conduits.
For this purpose, on the external wall near the stove, a hole must be

made with a minimum free cross-section of 100 cm². (equivalent to a

round hole of 12 cm diameter or a square hole 10x10 cm), protected by

a grille on the inside and the outside.
The air intake must also:

communicate directly with the room where the stove is installed

be protected by a grille, metal mesh or suitable guard, as long as

this does not reduce the cross-section below the minimum.

be positioned in such a way as to be impossible to obstruct

It is not compulsory to connect the air inlet of the

stove directly with the exterior, but an air flow must

be guaranteed of at least 50 m³/h. Refer to current

standards.

Figure 6 – Air intake grille

This manual is related to the following products: