2-48 / Installation & Operation

CI-ControlWave EFM

2.3.9.3.2 Tilt Angle


30/40 Watt Solar Panel Systems (see Figure 2-35) have adjustable tilt angles. Table 2-17
shows the angle (from horizontal) at which the Solar Panel should be installed in order to
maximize annual energy output. At most latitudes, performance can be improved by less of
an angle during the summer and more of an angle during the winter.

Table 2-17 - Solar Panel Tilt Angle for 40 Watt & 30 Watt Solar Panels

LATITUDE INSTALLATION ANGLE

0-4°

10° from Horizontal

5-20°

Add 5° to the Local Latitude

21-45°

Add 10° to the Local Latitude

46-65°

Add 15° to the Local Latitude

66-75°

80° from Horizontal


2.3.9.4 Installing the Rechargeable Battery and Solar Panel Harness


The Rechargeable Sealed Lead-acid Battery must be removed from its shipping carton and
installed on its mounting bracket within the enclosure as illustrated in Figure 2-36.