6.0 Troubleshooting

6.1 Troubleshooting

Tips

6.1.1 Inverter

Problems:

• Inverter turned on, the INV LED on the remote is blinking, no

output: Inverter is in Search mode. Either defeat Search mode—if not

needed—or turn on loads greater than the Search Watts setting.

6.1.2 Charger

Problems:

• Unit won’t transfer to Charge mode with AC applied: Measure the

input AC voltage, it should be 120VAC +/- 20 VAC, (export models: 230 VAC

+/- 40 VAC). Also, check that the VAC Dropout setting on the remote is 80

VAC (150 VAC for export models) or less.
• Transfer relay closes, and then opens and continues to cycle: AC

voltage is too low, or has transients that drop the AC voltage momentarily.

Change the VAC Dropout setting to 60 VAC and check for improvements. If

the cycling continues, back off the Charge Rate setting from 100% to 10%.
This cycling may also occur if the AC output of the inverter is connected to

the inverter’s AC input—check for proper input and output AC wiring. Check

the remote for indication of a fault.
• Charger not charging even though the remote says “Charging”:

Full charge rates are not obtained in Charge status, only after this mode

changes to “Bulk”, “Absorb,” or “Float”.
• Charger not charging even though the remote says “Bulk” (or

“Absorb”): Check the DC amps meter and the DC voltmeter on the ME-

MR display. It should be 80% or more of rated charge current if the battery

voltage is under 14.0 VDC (28.0 VDC on 24-volt models or 48.0 VDC for

48-volt models). If not, check the Charge Rate setting and verify the setting

is 80% or greater. Still low charge rate? Check the AC IN setting to verify

the setting. If no AC loads are being passed through the inverter, the AC IN

setting must be 15 amps (25 amps for 3kW unit) or greater, to receive a full

charge rate.
• Remote displays “Float” not “Bulk” when the AC is fi rst plugged

in: Check DC volts on the ME-MR display, if the battery is over 13.0 VDC

(26.0 VDC for 24-volt models or 52.0 VDC for 48-volt models) then the

battery was already charged and the charger automatically goes to Float

Charging to keep from overcharging the batteries.
• Charge amps are lower than expected, or is 0 amps DC: Measure

input AC voltage and increase if the input voltage is under 90 VAC. The

charge rate is reduced to try and keep the input voltage above 90 VAC; also

check the AC IN and Charge Rate settings to determine if the current is being

limited.

Charger output voltage is higher than expected: Check the Battery

Temperature Sensor (BTS) temperature. If the BTS is installed, the charge

voltage settings will increase if the temperature around the BTS is below 77°

F (25° C), and decrease if the temperature around the BTS is higher than

77° F (25° C).