3.0 Setup

3.2

Remote Menu Items

This section covers the function of each menu item and explains what con-

fi gurable settings are available from each menu.

3.2.1 AC IN Menu

Use this menu as a quick means of changing your AC IN setting to coordinate

with the circuit breaker rating from the incoming AC source.
• AC

IN

– This selection ensures the inverter’s AC loads receive the maxi-

mum current available from the utility or your generator power. Whenever

the utility or generator is connected to the inverter, the current used to

power the AC loads and to charge the batteries is monitored. When the

total current used to power the AC loads and charge the batteries begins

to approach the AC IN setting, the current that was used for charging

the batteries will automatically be reduced. This ensures the AC loads

have all the available current when needed. The feature is not available

on MM and MMS Series inverter/chargers.
Default setting: AC IN = 30 Amps
Range: 5 Amps, 15 Amps, 30 Amps, 50 Amps

Where to set: Adjust the AC IN setting to match the current rating of the

utility power or the generator’s circuit breaker. If using multiple AC sources

(utility and generator) through an AC transfer switch, adjust this setting to

the smaller AC breaker size. This setting is dependent on the stability of the

AC source. If using a generator, factors such as altitude and output voltage

regulation may require a lower setting than the generator’s breaker size. If

the breaker on the AC source is tripping (because it is a weak breaker), try

reducing this setting to the next lower level.

Note: If the ME-MR is connected to a MSH-RE inverter, the AC IN setting

applies to both inputs (AC1 and AC2).

CAUTION: The AC IN setting does not limit the current to the

inverter loads. If the current to the loads on the output of the in-

verter are greater than the circuit breaker rating on the incoming

AC source, you may experience nuisance tripping of this breaker.

Bottom line shows

current “saved” setting

If this setting is correct,

press MENU button to

access different menu items

If a different setting

is required:

press

press

press

To save the current

setting displayed:

ON/OFF

CHANGE

MENU

HOME

SAVE

HOLD

AC IN

30 Amps

AC IN

30 Amps

AC IN

5 Amps

AC IN

15 Amps

AC IN

50 Amps

Figure 3-2, AC IN Selections