3.0 Setup

3.2.6 Low Battery Cut-Out (LBCO) Menu

• LBCO

This menu is used to set the DC voltage level that turns off

the inverter to help protect the batteries from over-discharge damage.

Selections are from 9 VDC to 11 VDC (12-volt inverter models), 18 VDC

to 22 VDC (24-volt inverter models), or 36 VDC to 44 VDC (48-volt

inverter models). If the battery voltage drops below the LBCO selected

setpoint continuously for more than one minute, the FAULT LED will

come on, the inverter will turn off, and the display shows “FAULT! Low

Bat” (low battery status). If the battery voltage falls below 8.5 volts (12-

volt models), 17.0 volts (24-volt models) or 34.0 (48-volt models), the

FAULT LED and Low Bat status will be immediate.
Default settings: LBCO = 10 VDC (12-volt models), 20 VDC (24-volt

models) or 40 VDC (48-volt models).
Range: 9 VDC, 10 VDC, 11 VDC (12-volt models, x2 for 24v, x4 for 48v)

Info: The inverter will automatically begin to start inverting when

the DC voltage increases to ≥ 12.5 VDC (12-volt models), ≥ 25.0

VDC (24-volt models) or ≥ 50.0 VDC (48-volt models). If AC power

is available and connected to the inverter’s input the inverter will

automatically clear the Low Battery fault, pass the input AC power

to the output, and begin charging the batteries.

Where to set: To cycle the batteries slightly but not discharge them more

than 20%*, the LBCO setting should be set to 11 VDC (12-volt models), 22

VDC (24-volt models) or to 44 VDC (48-volt models). In some applications,

such as installations in an off-grid home or when doing a lot of dry-camping

in your RV, you may want to cycle down to 25%* by setting the LBCO to

10 VDC (12-volt models), 20 VDC (24-volt models) or to 40 VDC (48-volt

models). In extreme circumstances, you have the ability to discharge the

batteries to 80%* by setting the LBCO to 9 VDC (12-volt models), 18 VDC

(24-volt models), or to 36 VDC (48-volt models) before recharging.
* These discharge percentages are rough estimates; for accurate battery monitoring,

a battery monitor such as Magnum’s ME-BMK and the ME-RC remote is required.

Info: The inverter will automatically begin to start inverting when the

DC voltage increases to ≥ 12.5 VDC (12-volt models), ≥ 25.0 VDC

(24-volt models) or to ≥ 50.0 VDC (48-volt models). If AC power

is available and connected to the inverter’s input, the inverter will

automatically clear the Low Battery fault, pass the input AC power

to the output, and begin charging the batteries.

Bottom line shows

current “saved” setting

If this setting is correct,

press MENU button to

access different menu items

If a different setting

is required:

press

press

press

To save the current

setting displayed:

ON/OFF

CHANGE

MENU

HOME

SAVE

HOLD

LBCO

10 VDC

LBCO

10 VDC

LBCO

9 VDC

LBCO

11 VDC

Note: Values shown are for a 12-volt inverter

Figure 3-7, LBCO: Low Battery Cut-Out Selections