3.0 Setup

3.2.4 Battery Type Menu

• BAT

TYPE

– This menu is used to select the battery type, which

determines the battery charge profi le and ensures the batteries are

receiving the proper charge voltage. The fi xed voltage options are: GEL

(for Gel batteries), Flooded (for liquid lead acid batteries), AGM 1 (for

Lifeline AGM batteries), and AGM 2 (for East Penn/Deka/Discover/Trojan

AGM batteries). Refer to Table 3-3 to determine the specifi c charge

voltage based on the battery type selected.
Default setting: BAT TYPE = Flooded

Info: The voltage settings shown in Table 3-3 are based on the

Battery Temperature Sensor (BTS) being disconnected, or at a

temperature of 77° F (25° C). If the BTS is connected, the actual

charge voltage increases if the temperature around the BTS is colder

than 77° F (25° C), and decreases if hotter than 77° F (25° C). This

ensures the batteries receive the correct charge voltage even if they

become cold or hot.

Table 3-3, Battery Type to Charge Voltages

Battery

Type

Inverter

Voltage

Absorption

Voltage

Float

Voltage

Equalization

Voltage

GEL

12 VDC

14.1 VDC

13.6 VDC

14.1 VDC

1

24 VDC

28.2 VDC

27.2 VDC

28.2 VDC

1

48 VDC

56.4 VDC

54.4 VDC

56.4 VDC

1

Flooded

12 VDC

14.6 VDC

13.4 VDC

15.5 VDC

24 VDC

29.2 VDC

26.8 VDC

31.0 VDC

48 VDC

58.4 VDC

53.6 VDC

62.0 VDC

AGM 1

2

12 VDC

14.3 VDC

13.1 VDC

15.5 VDC

24 VDC

28.6 VDC

26.2 VDC

31.0 VDC

48 VDC

57.2 VDC

52.4 VDC

62.0 VDC

AGM 2

3

12 VDC

14.5 VDC

13.5 VDC

14.5 VDC

1

24 VDC

29.0 VDC

27.0 VDC

29.0 VDC

1

48 VDC

58.0 VDC

54.0 VDC

58.0 VDC

1

Note 1: Voltage same as absorption voltage – to prevent equalization.

Note 2: Specifi cations for Concord (Lifeline Series) AGM batteries.

Note 3: Specifi cations for East Penn, Deka, Discover and Trojan AGM batteries.

Figure 3-5, Battery Type Selections

Bottom line shows

current “saved” setting

If this setting is correct,

press MENU button to

access different menu items

If a different setting

is required:

press

press

press

To save the current

setting displayed:

ON/OFF

CHANGE

MENU

HOME

SAVE

HOLD

BAT TYPE

GEL

BAT TYPE

Flooded

BAT TYPE

AGM 1

BAT TYPE

Flooded

BAT TYPE

AGM 2