4 battery type menu, Menu, Save – Magnum Energy ME-MR Remote User Manual
Page 16: 0 setup, On/off

10
©2013 Magnum Energy, Inc.
3.0 Setup
3.2.4 Battery Type Menu
• BAT
TYPE
– This menu is used to select the battery type, which
determines the battery charge profi le and ensures the batteries are
receiving the proper charge voltage. The fi xed voltage options are: GEL
(for Gel batteries), Flooded (for liquid lead acid batteries), AGM 1 (for
Lifeline AGM batteries), and AGM 2 (for East Penn/Deka/Discover/Trojan
AGM batteries). Refer to Table 3-3 to determine the specifi c charge
voltage based on the battery type selected.
Default setting: BAT TYPE = Flooded
Info: The voltage settings shown in Table 3-3 are based on the
Battery Temperature Sensor (BTS) being disconnected, or at a
temperature of 77° F (25° C). If the BTS is connected, the actual
charge voltage increases if the temperature around the BTS is colder
than 77° F (25° C), and decreases if hotter than 77° F (25° C). This
ensures the batteries receive the correct charge voltage even if they
become cold or hot.
Table 3-3, Battery Type to Charge Voltages
Battery
Type
Inverter
Voltage
Absorption
Voltage
Float
Voltage
Equalization
Voltage
GEL
12 VDC
14.1 VDC
13.6 VDC
14.1 VDC
1
24 VDC
28.2 VDC
27.2 VDC
28.2 VDC
1
48 VDC
56.4 VDC
54.4 VDC
56.4 VDC
1
Flooded
12 VDC
14.6 VDC
13.4 VDC
15.5 VDC
24 VDC
29.2 VDC
26.8 VDC
31.0 VDC
48 VDC
58.4 VDC
53.6 VDC
62.0 VDC
AGM 1
2
12 VDC
14.3 VDC
13.1 VDC
15.5 VDC
24 VDC
28.6 VDC
26.2 VDC
31.0 VDC
48 VDC
57.2 VDC
52.4 VDC
62.0 VDC
AGM 2
3
12 VDC
14.5 VDC
13.5 VDC
14.5 VDC
1
24 VDC
29.0 VDC
27.0 VDC
29.0 VDC
1
48 VDC
58.0 VDC
54.0 VDC
58.0 VDC
1
Note 1: Voltage same as absorption voltage – to prevent equalization.
Note 2: Specifi cations for Concord (Lifeline Series) AGM batteries.
Note 3: Specifi cations for East Penn, Deka, Discover and Trojan AGM batteries.
Figure 3-5, Battery Type Selections
Bottom line shows
current “saved” setting
If this setting is correct,
press MENU button to
access different menu items
If a different setting
is required:
press
press
press
To save the current
setting displayed:
ON/OFF
CHANGE
MENU
HOME
SAVE
HOLD
BAT TYPE
GEL
BAT TYPE
Flooded
BAT TYPE
AGM 1
BAT TYPE
Flooded
BAT TYPE
AGM 2