3.0 Setup

3.2.5 Charge Rate Menu

• CHG

RATE

This selection is used to set the maximum charge rate

allowed to charge the batteries during Bulk, Absorption, Float, and

Equalize charging. The CHG RATE = 10% setting is available to help

minimize charging, while continuing to allow pass-through power.
Default setting: CHG RATE = 100%
Range: 10%, 50%, 100%

The charge rate selections are provided as a percentage of the inverter/

charger’s maximum charging capability. Refer to the label on the side of

the inverter or to the inverter/charger owner’s manual to determine its

maximum charge rate. Once you fi nd this maximum charge rate, determine

the percentage needed to limit the charge rate to your battery bank.

Example: If the maximum charge rate of your inverter/charger is 100

amps and you need to limit the charge rate to 50 amps, choose the CHG

RATE = 50% selection (50 amps = 50% of 100 amps).

Info: The topology of the Magnum inverter when connected to an

AC source overrides the setting, and starts charging if the battery

voltage is <12 VDC (12-volt models), <24 VDC (24-volt models)

or <48 VDC (48-volt models).

Where to set: The maximum charge rate is generally set to a C/5* rate (C =

the total amp-hour capacity of the battery bank—using the 20 hour AH rate).

The C/5 rate is usually used when the objective is to charge the batteries as

quickly as possible (i.e., 400 AH ÷ 5 = 80 amp maximum charge rate). A lower

rate such as C/20* is used when the batteries need to be charged as slow as

possible. The ME-MR provides three settings for charge rate adjustment—10,

50, and 100%. Multiply this percentage and the max charge rate of the

inverter to fi nd the closest setting to the desired charger output.

CAUTION: The C/5 or C/20 charge rate settings are guidelines;

they are not requirements on how you should set your battery

charge rate. For specifi c charge rate requirements, refer to your

battery manufacturer.
Info: If multiple inverter/chargers are used on a single battery

bank, you must ensure that the total charge rate from all inverter/

chargers is limited to the max charge rate needed for your battery

bank. This setting only limits the charging on each inverter/charger

individually, not on all inverter/chargers.

* C/5 or C/20 rate – Charge rates are commonly expressed as a ratio of the total

amp-hour (AH) capacity of the battery bank. For example, with a 400 AH battery

bank (C = 400), the C/5 charge rate is 80 A (400/5 = 80 A).

Bottom line shows

current “saved” setting

If this setting is correct,

press MENU button to

access different menu items

If a different setting

is required:

press

press

press

To save the current

setting displayed:

ON/OFF

CHANGE

MENU

HOME

SAVE

HOLD

CHG RATE

100%

CHG RATE

10%

CHG RATE

100%

CHG RATE

50%

Figure 3-6, Charge Rate Selections