If you have a fault during the Power Saver mode, the LCD backlight, and the
FAULT LED will come on and stay on as long as the fault is detected. If you
want the LCD backlight and LEDs to always be on, select PWR SAVE = Off.
Bottom line shows
current “saved” setting
If this setting is correct,
press MENU button to
access different menu items
If a different setting
is required:
press
press
press
To save the current
setting displayed:
ON/OFF
CHANGE
MENU
HOME
SAVE
HOLD
PWR SAVE
On
PWR SAVE
Off
PWR SAVE
On
3.2.9 Equalize
Menu
• EQUALIZE
– This menu allows you to equalize the batteries after a Float
Charge is achieved. Equalizing should only be attempted by experienced
users.
Default setting: EQUALIZE = Disabled
Range: Disabled, Request, EQing
What is equalizing? Equalizing is a controlled overcharge of the batteries.
During this process, there will be excessive gassing of the batteries. This
condition is not only corrosive, but can also be dangerous as hydrogen
gasses are emitted during the charging process.
WARNING: Only equalize in well ventilated areas. Consult your
battery’s manufacturer for recommendations on equalizing.
Info: Equalization can only be accomplished when the charger status
is “FLOAT” or “Full Chg”.
Info: Equalization charging is not available if either GEL or AGM 2 is
selected from the Battery Type menu.
Bottom line shows
current “saved” setting
If this setting is correct,
press MENU button to
access different menu items
To start
equalization:
press
press
ON/OFF
CHANGE
MENU
HOME
EQUALIZE
Disabled
EQUALIZE
Disabled
EQUALIZE
EQing
EQUALIZE
Request
Figure 3-9, Power Saver Selections
Figure 3-10, Equalize Selections