Menu, 0 setup – Magnum Energy ME-MR Remote User Manual

Page 23

background image

©2013 Magnum Energy, Inc.

17

3.0 Setup

Table 3-4, ME-MR’s Inverter/Charger Default Settings

Menu

Default Setting

AC In

AC IN = 30 Amps

Search Watts

SEARCH = 5 Watt

Battery Amp-Hours

BAT AHRS = 400 AH

(Absorb Time = 90 min.)

Battery Type

BAT TYPE = Flooded

Charge Rate

CHG RATE = 100%

Low Battery Cut Out

LBCO = 10 VDC (12-volt models),

20 VDC (24-volt models),

40 VDC (48-volt models)

Low VAC Dropout

VAC DROP = 80 VAC (150 VAC for export)

Power Save

PWR SAVE = On (15 min.)

Equalize

EQUALIZE = Disabled

Charger Standby

CHARGER = No AC In

(Charger Standby is off, will automatically

charge when AC is connected)

Power On

POWER ON = Norm

TECH: SETUP

SETUP = Unlock

Defaults: This menu restores all settings on the ME-MR (and in the in-

verter/charger) to the original factory default settings. To restore, press

and hold the SAVE/HOLD button for 5 seconds (see Figure 4-1). After

the default settings have been restored, the display will show “Loaded”.

The ME-MR factory defaults are listed in Table 3-4.

Figure 3-13, TECH Menus

Press the ON/OFF button to

to view TECH menus

TECH menus are “read only”

displays, no changes can be

made to these screens*/**

To scroll next

screen:

press

press

ON/OFF

CHANGE

MENU

HOME

* Press and hold the SAVE/HOLD button to restore defaults

**Press the SAVE/HOLD button to select Lock or Unlock

TECH

Press ON

Bat Temp

xx C

Xfm Temp

xx C

FET Temp

xx C

Inverter
Rev x.x

Model

xxxxxx

Ext Ctrl

No

SETUP**

Lock

Remote

Rev 1.1

Defaults*

5.0 secs