5.0 Operation

FAULT !
Bridge

Bridge appears on the LCD and

the FAULT (red) LED is on. The INV

(green) LED is off.

Figure 5-34, Internal Bridge Fault

5.3.3.3 Internal Fault Messages

The inverter continually monitors several internal components. If a condition

inside the inverter occurs that does not allow proper operation, the inverter

shuts down to protect itself. An inverter reset is required to clear these faults.

Remedy: Perform an inverter reset (see Section 6.2). After resetting

the inverter, press the ON/OFF button to turn the inverter on and to

verify the fault has cleared. If the internal fault remains, the inverter

may require repair at an authorized service facility.

FAULT !
CHARGER

CHARGER appears on the LCD and

the FAULT (red) LED is on. The INV

(green) LED is off.

Figure 5-35, Internal Charger Fault

• Internal

Charger Fault – The inverter shuts down because the internal

charger protection circuit has been activated.

FAULT !
NTC Snsr

NTC Snsr appears on the LCD and

the FAULT (red) LED is on. The INV

(green) LED is off.

Figure 5-36, Internal NTC Sensor Fault

• Internal

Bridge Fault – The inverter shuts down because the internal

power-bridge protection circuit has been activated.

• Internal NTC Sensor Fault – The inverter shuts down because the

internal NTC (temperature sensor) circuit has been activated.