6.0 Troubleshooting

6.0 Troubleshooting

If the remote is not functioning correctly, use the following table to help fi nd

a solution.

Table 6-1, Remote Troubleshooting

Symptom

Possible Cause

Solution

Display shows

unrecognizable

letters or

symbols.

Static electricity

may have been

discharged into the

LCD display.

Refresh display: Press and

hold the MENU/HOME button for

10 seconds.

The LCD text

display is

locked-up,

pressing any

button has

no response

- may show

“revision” or

“connecting”.

The RJ11

connections on the

communication cable

are not making a

good connection.

Reset remote: 1) disconnect

the remote cable from the

inverter for 5 seconds and

then reconnect; 2) check RJ11

cable connection on back of the

remote (see Figure 2-2).
Important: Ensure the RJ11

connector is pushed into

the correct port. You should

feel/hear “click” when the

connection is made.

The remote is not

getting suffi cient

power from the

inverter.

Ensure the inverter batteries

are connected and the inverter

is operating correctly. The

inverter should be able to invert

and power AC loads from the

batteries (ensure no AC power

is connected to the inverter’s AC

inputs).

The LEDs and

the backlight

are off.

The remote is in

Power Saver mode.

Press any button to reactivate

the remote (or turn the Power

Saver setting to Off).

The remote is

non-functional

(no lights, no

text on LCD

display, and no

response when

pressing any

button).

The communication

cable is bad or not

correctly connected

to the Remote port

on the inverter.

Check the communications

cable from the inverter to

remote; ensure: 1) it is

connected to the Remote port,

2) the correct communications

cable is used (a 4-conductor

telephone cable may be

substituted to determine if cable

is good).

Inverter is not

connected to

batteries.

Ensure inverter batteries are

connected and the inverter is

operating correctly without any

AC power connected (should

be able to invert and power AC

loads from batteries).