beautypg.com

Fault ! low batt, Fault ! no comm – Magnum Energy ME-MR Remote User Manual

Page 36

background image

30

©2013 Magnum Energy, Inc.

5.0 Operation

Low Batt appears on the LCD and

the FAULT (red) LED is on. The INV

(green) LED is off.

Figure 5-24, Low Battery Fault

• Low

Battery

Fault

– The inverter turns off to prevent the batteries from

being over-discharged. The FAULT LED illuminates when the battery voltage

drops below the LBCO setting for >1 minute. The inverter automatically

restarts and resumes operation when the battery voltage rises to ≥12.5 VDC

(12v models), ≥25.0 VDC (24v models), or ≥50.0 VDC (48v models).

Remedy: This fault will also automatically restart if AC power (such

as utility/shorepower or a generator) is connected to the inverter/

charger’s input and battery charging begins.

FAULT !
Low Batt

• No

Comm – Remote is not receiving any information from the inverter.

Remedy: Reset the remote by disconnecting the remote commu-

nications cable from the inverter for 5 seconds, and then reconnect

it (see Figure 2-3). If the fault continues, fi rst check/replace the

remote cable. This cable is 4-wire telephone cable.

Figure 5-25, No Communication

FAULT !
No Comm

No Comm appears on the LCD.

FAULT (red) LED is off. INV (green)

LED may be off or on. Ignore the

INV LED.

High Volts AC Fault – Charger is disabled due to a very high AC voltage

(>150 VAC, >260 VAC – export models) detected on the AC input.

Remedy: Remove all AC power from the inverter’s AC input for at

least 15 minutes to automatically restart this fault. Ensure only 120

VAC power is connected to each of the inverter’s AC inputs. Check

and correct the high voltage problem from the source.

FAULT !
High VAC

High VAC appears on the LCD and

the FAULT (red) LED is on. The INV

(green) LED is off.

Figure 5-23, High Volts AC Fault