beautypg.com

7 vac dropout menu, 8 power save menu, Menu – Magnum Energy ME-MR Remote User Manual

Page 19: Save, 0 setup, On/off

background image

©2013 Magnum Energy, Inc.

13

3.0 Setup

3.2.7 VAC Dropout Menu

• VAC

DROP

– This selection is used to set the minimum AC voltage that

must be present on the input before the inverter/charger switches from

Invert to Charge mode. For example, if this setting is set to VAC DROP

= 60 VAC, then the AC input voltage must be above 60 volts before the

inverter will switch from Invert mode to Charge mode. This setting also

determines the minimum AC voltage threshold where the inverter/char-

ger transfers from the AC input (utility/shore or generator) and begins

inverting. This protects AC loads from utility outages.
Default setting: VAC DROP = 80 VAC for North American units; 150

VAC for export models.
Range: 60 VAC, 80 VAC, and 100 VAC for 120v units (North America);

and 110 VAC, 150 VAC, and 190 VAC for 230v units (for export)

Where to set: It depends on the application and what you are using as the

AC source. The settings not only look at the incoming voltage to determine

when to transfer, but they also determine the response sensitivity to incoming

voltage fl uctuations. Use the 100 VAC dropout setting when the AC source

is well regulated and you are operating devices that are sensitive to voltage

fl uctuations. Use the 80 VAC or lower setting (60 VAC) when the AC source

may have signifi cant fl uctuations in RMS voltage. These settings are highly

recommended if using a generator for charging.

Note: If the ME-MR is connected to a MSH-RE inverter, the VAC Dropout

setting applies to both inputs (AC1 and AC2).

Figure 3-8, VAC Dropout Selections

Bottom line shows

current “saved” setting

If this setting is correct,

press MENU button to

access different menu items

If a different setting

is required:

press

press

press

To save the current

setting displayed:

ON/OFF

CHANGE

MENU

HOME

SAVE

HOLD

VAC DROP

80 VAC

VAC DROP

80 VAC

VAC DROP

100 VAC

VAC DROP

80 VAC

3.2.8 Power Save Menu

• PWR

SAVE – This setting allows you to turn the Power Save feature

on or off.
Default setting: PWR SAVE = On
Range: On, Off

What is the Power Saver feature? The Power Saver feature causes the

LCD backlight and LEDs on the remote display to turn off to conserve energy.

The remote goes into Power Saver mode if there has not been a button press

or fault message for 15 minutes. Whenever the remote goes into the Power

Saver mode, the LCD backlight and LEDs can be reactivated by pressing any

button on the remote.