5.0 Operation

5.3.2 Charger Mode Messages

When AC power (utility or generator) is connected to the inverter/charger, it

begins to monitor the AC input for acceptable voltage. Once the AC input is

accepted, the AC transfer relay (inside the inverter) closes and Charge mode

begins. There are several Charge mode messages; view the LCD display and

the corresponding message in this section to identify and understand the

particular Charge mode.

Info: The AC input becomes acceptable after a minimum 10-second

delay, and when the voltage is greater than the VAC Dropout setting.

• Absorb

Charging Mode – The Absorb stage is the constant voltage

stage and begins when the absorb voltage is reached (determined by

the Battery Type setting) while Bulk Charging. During this stage, the DC

charging current decreases as the battery becomes charged. This Charge

stage continues until the absorb charging time (determined by the Battery

Amp-Hours setting) is fi nished.

Absorb appears on the LCD. The FAULT

(red) LED is off, and the INV (green) LED

could be on or off.

STATUS
Absorb

Figure 5-6, Absorb Charging Mode

• Searching Mode – When the inverter is in Search mode, the AC loads

on the inverter output are less than the Search Watts setting. The Search

mode function is used to reduce the inverter draw from the battery, and may

be turned off whenever you want full inverter output voltage available at all

times.

STATUS
Search

Search appears on the LCD. The

INV (green) LED slowly fl ashes. The

FAULT LED (red) is off.

Figure 5-5, Searching Mode

STATUS
Off

• Off

Mode

– This message tells you that there is no AC available on the

inverter’s AC output. The inverter function is off.

Figure 5-4, Off Mode

Off appears on the LCD. All LEDs

are off.