3.3 I/O Signal Connections
3-23
3
Wi
ring and
C
onne
ctio
n
3.3 I/O Signal Connections
This section describes the names and functions of I/O signals (CN1). Also connection examples by control
method are shown.
3.3.1 I/O Signal (CN1) Names and Functions
The following table shows the names and functions of I/O signals (CN1).
(1) Input Signals
Note 1. The allocation of the input signals (P-OT, N-OT, /SI1, /SI4 to /SI6) can be changed. For details, refer to 3.4.1
Input Signal Allocations.
2. If the Forward run prohibited/ Reverse run prohibited function is used, the SERVOPACK or converter is stopped
by software controls, not by electrical or mechanical means. If the application does not satisfy the safety require-
ments, add an external circuit for safety reasons as required.
• The number of pins on the CN1 connector is different on a large-capacity
Σ-V SER-
VOPACK (50 pins) and a standard
Σ-V SERVOPACK (26 pins). If you are using both
types of SERVOPACK, use the correct connector model numbers when ordering and
the correct signal assignments.
• Regarding the allocation and use of I/O signals, they differ in accordance with the
connected option module. For details, refer to the manual for the command option
module that is connected.
Signal Pin No.
Name
Function
Refer-
ence
Section
P-OT
N-OT
42
43
Forward run
prohibited,
Reverse run
prohibited
With overtravel prevention: Stops servomotor when movable
part travels beyond the allowable range of motion.
4.2.2
/SI1
41
Command option
module input 1
Connects the external input signal used in the command
option module.
−
/SI4
/SI5
/SI6
44
45
46
Command option
module input 4
Command option
module input 5
Command option
module input 6
Connects the external input signal used in the command
option module.
−
/SI0
40
General-purpose input
signal
Connects the external input signal used in the command
option module.
−
+24VIN 47
Control power supply
for sequence signal
Control power supply input for sequence signals.
Allowable voltage fluctuation range: 11 to 25 V
Note: The 24 VDC power supply is not included.
3.5.1
BAT (+)
BAT (-)
21
22
Battery (
+) input signal
Battery (-) input signal
Connecting pin for the absolute encoder backup battery.
Do not connect when the encoder cable with the battery case
is used.
3.7.2
4.5.1
/P-CL
/N-CL
/DBANS
Can be
allocated
Forward external
torque limit
Reverse external
torque limit
Dynamic brake answer
signal
The allocation of an input signal to a pin can be changed in
accordance with the function required.
−