9.2 Warning Displays
9-25
9
Trou
blesh
ooting
A.920:
Regenerative
Overload
(Warning before
the alarm A.320
occurs)
The power supply volt-
age exceeds the speci-
fied limit.
Measure the power supply voltage.
Set the power supply voltage within
the specified range.
Insufficient regenera-
tive resistance, regener-
ative resistor capacity,
SERVOPACK capacity,
or converter capacity.
Or, regenerative power
has been continuously
flowing back.
Check the operating condition or the
capacity using the capacity selection
Software SigmaJunmaSize+, etc.
Change the regenerative resistance,
regenerative resistor capacity, SER-
VOPACK capacity, or converter
capacity. Reconsider the operating
conditions using the capacity selection
software SigmaJunmaSize+, etc.
Regenerative power
continuously flowed
back because negative
load was continuously
applied.
Check the load to the servomotor dur-
ing operation.
Reconsider the system including servo
drives, machine, and operating condi-
tions.
A.921:
Dynamic Brake
Overload
(Warning before
the alarm A.731
occurs)
The servomotor rotates
because of external
force.
Check the operation status.
Take measures to ensure the servomo-
tor will not rotate because of external
force.
The rotating energy at a
DB stop exceeds the DB
resistance capacity.
Check the power consumed by DB
resistance (Un00B) to see how many
times the DB has been used.
Reconsider the following:
• Reduce the motor reference speed.
• Reduce the moment of inertia ratio.
• Reduce the number of times of the
DB stop operation.
A fault occurred in the
SERVOPACK or con-
verter.
−
The SERVOPACK or converter may
be faulty. Replace the SERVOPACK
or converter.
A.930:
Absolute
Encoder Battery
Error
(The absolute
encoder battery
voltage is lower
than the specified
value.)
∗ Only when an
absolute encoder
is connected.
The battery connection
is incorrect.
Check the battery connection.
Reconnect the battery.
The battery voltage is
lower than the specified
value 2.7 V.
Measure the battery voltage.
Replace the battery.
A fault occurred in the
SERVOPACK.
−
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A.94A
Command
Option Module
IF Data Setting
Warning 1
An incorrect parameter
number was sent to the
SERVOPACK from the
host controller or com-
mand option module.
–
Specify the correct parameter number.
A.94B
Command
Option Module
IF Data Setting
Warning 2
Out-of-range data was
sent to the SERVO-
PACK from the host
controller or command
option module.
–
Specify the value of the parameter
within the allowable range.
A.94C
Command
Option Module
IF Data Setting
Warning 3
Incorrect parameter data
was sent to the SERVO-
PACK from the host
controller or command
option module.
–
Specify the value of the parameter
within the allowable range.
(cont’d)
Warning Num-
ber: Warning
Name (Warning
Description)
Cause
Investigative Actions
Corrective Actions