8.2 SERVOPACK and Converter Startup Procedure

8-13

8

Fu

lly-close

d L

oop

Co

ntro

l

3

Check the external encoder.

Item to Check

• Are signals from the external

encoder received correctly?

Set parameters related to the fully-
closed loop control and move the
machine with your hand without
turning ON the power supply to the

servomotor. Check the following
status with the digital operator or
SigmaWin+.

• Does the fully-closed feedback

pulse counter (Un00E) count up
when the servomotor moves in
the forward direction?

• Is the distance the machine

moved about visually the same

as the amount counted by the
fully-closed feedback pulse
counter (Un00E)?

Note: The unit for fully-closed

feedback pulse counter
(Un00E) is one pulse, which
is equivalent to the external
encoder sine wave pitch
divided by the number of
divisions

*

.

∗ Refer to 8.3.5 Electronic Gear

for details on the number of
divisions.

• External Encoder Usage

(Pn002.3)

• Number of External Scale

Pitch (Pn20A)

• Electronic Gear Ratio

(Numerator) (Pn20E)

• Electronic Gear Ratio

(Denominator) (Pn210)

• Encoder Output Resolution

(Pn281)

• Excessive Error Level

Between Servomotor and
Load Positions (Pn51B)

• Positioning Completed

Width (Pn522)

• Multiplier per One Fully-

closed Rotation (Pn52A)

4

Perform a program JOG opera-
tion.

Items to Check

• Does the fully-closed loop

control operate correctly when
operating the SERVOPACK in
standalone mode?

Perform a program JOG operation
and check that the distance that the
servomotor moved is the same as
the distance that is set in Pn531.
Note: Start from a low speed and

gradually increase the speed.

• Program JOG related param-

eters (Pn530 to Pn536)

SERVOPACK

5

Operate the SERVOPACK and
converter.

Items to Check

• Does the fully-closed loop

control operate correctly
including the host controller?

Input the position reference and
check that the SERVOPACK and
converter operate correctly.
Note: Start from a low speed and

gradually increase the speed.

Host controller

(cont’d)

Procedure

Description

Operation

Parameters Requiring

Settings

Controller