9.2 Warning Displays

9-27

9

Trou

blesh

ooting

A.971:
Undervoltage

The AC power supply
voltage dropped to:

• 140 V or less for 200-

VAC SERVOPACKs.

• 280 V or less for 400-

VAC SERVOPACKs.

Measure the power supply voltage.

Set the power supply voltage within
the specified range.

The power supply volt-
age dropped during

operation.

Measure the power supply voltage.

Increase the power supply capacity.

Occurrence of instanta-
neous power interrup-
tion.

Measure the power supply voltage.

When the instantaneous power cut
hold time (Pn509) is set, decrease the
setting.

A fault occurred in the
SERVOPACK or con-
verter.

The SERVOPACK or converter may
be faulty. Replace the SERVOPACK
or converter.

A.9A0:
Overtravel
(Overtravel status
is detected.)

When the servomotor
power is ON, over-
travel status is detected.

Check the input signal monitor
(Un005) to check the status of the
overtravel signals.

Refer to 9.3 Troubleshooting Malfunc-
tion Based on Operation and Condi-

tions of the Servomotor. Even if
overtravel signals were not shown by
the input signal monitor (Un005),
momentary overtravel may have been
detected. Take the following precau-
tions.

• Do not specify movements that

would cause overtravel from the
host controller.

• Check the wiring of the overtravel

signals.

• Take countermeasures for noise.

(cont’d)

Warning Num-

ber: Warning

Name (Warning

Description)

Cause

Investigative Actions

Corrective Actions