9 Troubleshooting
9.1.2 Troubleshooting of Alarms
9-18
A.CF2:
Feedback Option
Module
Communications Error
(Timer stop)
Noise interferes with the cable
between serial converter unit and
SERVOPACK.
−
Correct the wiring around serial
converter unit, e.g., separating I/O
signal line from main circuit cable
or grounding.
A serial converter unit fault
occurred.
−
Replace the serial converter unit.
A fault occurred in the SERVO-
PACK.
−
Replace the SERVOPACK.
A.d00:
Position Error
Overflow
(Position error exceeded
the value set in the
excessive position error
alarm level (Pn520).)
The servomotor U, V, and W wir-
ings is faulty.
Check the servomotor main circuit
cable connection.
Confirm that there is no contact
fault in the motor wiring or encoder
wiring.
The position reference speed is
too high.
Reduce the reference speed, and
operate the SERVOPACK.
Reduce the position reference speed
or acceleration of position refer-
ence. Or, reconsider the electronic
gear ratio.
The acceleration of the position
reference is too high.
Reduce the reference acceleration,
and operate the SERVOPACK.
Reduce the reference acceleration
of the position reference.
Setting of the excessive position
error alarm level (Pn520) is low
against the operating condition.
Check the alarm level (Pn520) to
see if it is set to an appropriate
value.
Set the Pn520 to proper value.
A fault occurred in the SERVO-
PACK.
−
Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.
A.d01:
Position Error
Overflow Alarm at
Servo ON
This alarm occurs if the servomo-
tor power is turned ON when the
position error is greater than the
set value of Pn526 while the ser-
vomotor power is OFF.
Check the position error amount
(Un008) while the servomotor
power is OFF.
Correct the excessive position error
alarm level at servo ON (Pn526).
A.d02:
Position Error
Overflow Alarm by
Speed Limit at Servo
ON
When the position errors remain
in the error counter, Pn529 limits
the speed if the servomotor power
is ON. If Pn529 limits the speed
in such a state, this alarm occurs
when position references are
input and the number of position
errors exceeds the value set for
the excessive position error alarm
level (Pn520).
−
Correct the excessive position error
alarm level (Pn520).
Or, adjust the speed limit level at
servo ON (Pn529).
A.d10:
Motor-load Position
Error Overflow
Motor rotation direction and
external encoder installation
direction are opposite.
Check the servomotor rotation
direction and the external encoder
installation direction.
Install the external encoder in the
opposite direction, or change the
setting of the external encoder
usage method (Pn002.3) to reverse
the direction.
Mounting of the load (e.g., stage)
and external encoder joint instal-
lation are incorrect.
Check the external encoder
mechanical connection.
Check the mechanical joints.
A.E00:
Command Option
Module IF Initialization
Timeout Error
The connection between the
SERVOPACK and the command
option module is faulty.
Check the connection between the
SERVOPACK and the command
option module.
Correctly connect the command
option module.
A command option module fault
occurred.
–
Replace the command option mod-
ule.
A SERVOPACK fault occurred.
–
Replace the SERVOPACK.
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause
Investigative Actions
Corrective Actions