beautypg.com

1) signals output during servomotor speed limit, 2) speed limit setting – Yaskawa Sigma-5 Large Capacity Users Manual: Design and Maintenance-Command Option Interface User Manual

Page 149

background image

4.6 Other Output Signals

4-53

4

Ope

rat

ion

(1) Signals Output during Servomotor Speed Limit

The following signal is output when the motor speed reaches the limit speed.

Note: Use parameter Pn50F.1 to allocate the /VLT signal for use. For details, refer to 3.4.2 Output Signal Allocations.

(2) Speed Limit Setting

Select the speed limit mode with Pn002.1.

Internal Speed Limit Function

If the internal speed limit function is selected in Pn002.1, set the limit of the maximum speed of the servomo-

tor in Pn407. The limit of the speed in Pn408.1 can be either the maximum speed of the servomotor or the

overspeed alarm detection speed. Select the overspeed alarm detection speed to limit the speed to the maxi-
mum speed of the servomotor or the equivalent.

Note: The servomotor’s maximum speed or the overspeed alarm detection speed will be used when the setting in this

parameter exceeds the maximum speed of the servomotor used.

External Speed Limit Function

If the external speed limit function is selected in Pn002.1, the motor speed is controlled by the speed limit

command. For details, refer to the manual of the connected command option module.

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Output

/VLT

Must be allocated

ON (closed)

Servomotor speed limit being applied.

OFF (open)

Servomotor speed limit not being applied.

Parameter

Meaning

When

Enabled

Classification

Pn002

n.

0

[Factory setting]

Disables the speed limit reference when torque limit is
used from the command option module. Uses the value
set in Pn407 as the speed limit (internal speed limit

function).

After restart

Setup

n.

1

Enables the speed limit reference when torque limit is
used from the command option module (external speed
limit function).

Pn407

Speed Limit During Torque Control

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 10000

1 min

-1

10000

Immediately

Setup

Torque

Parameter

Meaning

When

Enabled

Classification

Pn408

n.

0

[Factory setting]

Uses the smaller value of the maximum motor speed
and the value of Pn407 as the speed limit value.

After restart

Setup

n.

1

Uses the smaller value of the overspeed alarm detec-
tion speed and the value of Pn407 as speed limit value.