YASKAWA TM.iQp.02 iQpump Drive Programming Manual
83
■
Related Parameters
The following parameters need to be set correctly to insure proper operation of the iQpump drive when using Modbus communication.
Table 20 Serial Communication Related Parameters
Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:
1. Monitoring operation status of the Drive
2. Setting and reading iQpump drive parameters
3. Resetting faults
4. Input multi-function commands
Important: An OR operation is performed between the multi-function command input from the PLC and the command input from multi-
function digital input terminals S3 to S7.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
Number
b1-01
0108H
Frequency Reference
Selection
Reference Source
Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
0 to 3
0
Pump Quick
Setup
b1-02
0181H
Run Command
Selection
Run Source
Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
0 to 3
1
Pump Quick
Setup
H5-01
0425H
Drive Node Address
Serial Com Adr
Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note: An address of “0” disables serial com.
0 to 20
(H5-08=0)
0 to FF
(H5-08=1)
0 to 63
(H5-08=2)
1F
Programming
H5-02
0426H
Communication
Speed Selection
Serial Baud Rate
Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
0 to 4
3
Programming
H5-03
0427H
Communication
Parity Selection
Serial Com Sel
Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity
0 to 2
0
Programming
H5-04
0428H
Stopping Method
after Communication
Error
Serial Fault Sel
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3
3
Programming
H5-05
0429H
Communication
Error Detection
Selection
Serial Flt Dtct
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.
0 or 1
1
Programming
H5-06
042AH
Drive Transmit Wait
Time
Transmit WaitTIM
Sets the time from when the Drive receives data to when the Drive
sends data.
5 to 65
5 ms
Programming
H5-07
042BH
RTS Control
Selection
RTS Control Sel
Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0 or 1
1
Programming
H5-09
0435H
Communication
Error Detection Time
CE Detect Time
Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-
04.
0 to 10.0
(H5-08=0)
0 to 10.0
(H5-08=1)
0 to 90.0
(H5-08=2)
2.0 sec
Programming
*Set H5-01 to 0 to disable Drive responses to Modbus communications.