P3-12 delta setpoint feedback acc/dec changeover, Figure 122 – Yaskawa iQpump Programming Manual User Manual

Page 155

background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

155

Figure 1.117

Figure 122

P3-12 Delta Setpoint Feedback Acc/Dec Changeover

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can be configured for multiplex pumping operation. The acceleration (Acc) and deceleration (Dec) times can be

changed when the difference between the delta setpoint and feedback are within the programmed level in the Delta Setpoint Feedback

Acc/Dec Changeover (P3-12).

The acceleration and deceleration times during this changeover are programmed into C1-05 and C1-06, respectively.

This function is used to improve the pump regulation.

Setting P2-12 to a value of 0 will disable this function.

TIME

Output Frequency

Add Pump Delay Time P3-04

Feedback

Auto Mode Run

Multi-function

Output #40

Wait for Start

Max-Multi Level

P3-02

STOP, 0Hz

0%

OFF Mode

Start Level

P1-04

ADD PUMP 2

AUTO MODE RUN:

Start System, Incoming Run Command

Start System

Start Level Delay

P1-05

START DELAY

System

Set-Point

Add Pump Delay Time

P3-04

Multi-function

Output #41

ADD PUMP 3

PUMP 1

Multiplex Stabilize Time

P3-11

Multiplex Stabilize Time

P3-11

Lead/Lag Functions

Disabled until

stabilization timer

expires