beautypg.com

H5-04 stopping method after communication error, H5-05 communications error detection selection, H5-06 drive transit wait time – Yaskawa iQpump Programming Manual User Manual

Page 94: H5-07 rts control selection, H5-08 communication protocol selection

background image

94

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

It may be necessary to avoid the 19.2 K baud setting if frequent serial communications errors occur at that baud rate.

H5-04 Stopping Method after Communication Error

The setting of parameter H5-04 will determine the Drive’s reaction to a serial communications fault such as the CE fault. The iQpump

drive can be programmed to either ramp to a stop in the time specified by C1-02 (H5-04 = “0: Ramp to stop”), coast to a stop (H5-04 =

1), ramp to a stop at the special fast stopping time specified by C1-09 (H5-04 = “2: Fast-Stop”), or continue operating using the

commands received before the serial communication fault and flashing an alarm on the digital operator (H5-04 = “3: Alarm Only”).

H5-05 Communications Error Detection Selection

The iQpump drive can be configured by parameter H5-05 to recognize a CE fault whenever serial communications time-out. If H5-05 =

“1: Enabled,” the iQpump drive will fault if serial communication responses are not received within a set period of time determined by

parameter H5-09. iQpump drive power should be cycled after a change is made to this parameter.

H5-06 Drive Transit Wait Time

Setting Range:

5 to 65 ms

Factory Default: 5 ms

Parameter H5-06 will set the delay time between the receiving of a message from the master and the sending of a response from the

iQpump drive back to the master. The iQpump drive power should be cycled after a change is made to this parameter.

H5-07 RTS Control Selection

RTS or Request To Send control is a method of flow control applied to messaging in serial communications. Parameter H5-07 configures

whether the iQpump drive will implement RTS messaging all the time (H5-07 = “0: Disabled”) or only when sending (H5-07 = “1:

Enabled”). It is recommended to set H5-07 = “0: Disabled,” when using RS-485 and set H5-07 = “1: Enabled,” when using RS-422. The

iQpump drive power should be cycled after a change is made to this parameter.

H5-08 Communication Protocol Selection

Since the iQpump drive is capable of using MEMOBUS, Metasys N2, or Apogee FLN communications via the RS-485/422 terminals,

parameter H5-08 must be programmed to specify to the iQpump drive which format is being used. iQpump drive power should be cycled

after a change is made to this parameter.

Setting

Description

0

Ramp to Stop

1

Coast to Stop

2

Fast-Stop

3

Alarm Only (

factory default)

Setting

Description

0

Disabled

1

Enabled (

factory default)

Setting

Description

0

Disabled (RTS is always on)

1

Enabled (RTS turns on only when sending) (

factory default)

Setting

Description

0

Memobus (Modbus) (

factory default)

1

N2 (Metasys)

2

FLN (APOGEE)