Function: Thermostat Fault (Setting: 83)

A digital input can be configured to indicate a Thermostat Fault from an external contact (H1-0x = 83). A contact closure into the multi-

function input will enable the Thermostat Fault. After an initiation of a Thermostat Fault, to disable the Thermostat Fault requires a open

digital input contact, the drive run command to be open and reset the Thermostat Fault via the drive's reset button or fault reset input.

Note: An OPE12 fault will occur if H1-xx = 83 and 87. H1-xx cannot be programmed to “83” and “87” at the same time.

Figure 1.46

Figure 46 Thermostat Fault on Operator

Figure 1.47

Figure 47 Wiring Diagram

Function: Disable Pre-Charge (Setting: 84)

A digital input can be configured to enable or disable the Pre-Charge function (H1-0x = 84). A contact closure into the multi-function

digital input will disable the Pre-Charge function independent of the value programmed into the Pre-Charge Time (P4-03). When the

digital input is open, the Pre-Charge function is enabled.

-DRIVE-

Thermostat

THMS

U2-04 =
U2-05 =

0.00 Hz
0.00 A

External Switch or
Relay Contact

Thermostat Fault

H1-04 = 83
(Thermostat FltNo)

S1

S2

S3 (H1-01

S4 (H1-02)

S5 (H1-03)

S6 (H1-04)

S7 (H1-05)

SC

SP 24 VDC +/- 20%, 8 mA

E (G)

SN