B1-08 run command selection during programming, B1-11 drive delay time setting, Figure 12 coast to stop with timer – Yaskawa iQpump Programming Manual User Manual
Page 17: Ddly waiting to run

YASKAWA TM.iQp.02 iQpump Drive Programming Manual
17
Figure 1.12
Figure 12 Coast to Stop with Timer
■
b1-08 Run Command Selection During Programming
As a safety precaution, the iQpump drive will not normally respond to a Run input when the digital operator is being used to adjust
parameters. If it is necessary that external Run commands be recognized even while the Drive is being programmed, set b1-08 = “1:
Enabled.”
■
b1-11 Drive Delay Time Setting
Setting Range:
0 to 600 sec
Factory Default: 0 sec
If a time is set into parameter b1-11, the iQpump drive will delay executing any run command until the b1-11 time has expired. During
iQpump drive delay time execution, the digital operator will display:
Both the ALARM and Run indicators will blink while the iQpump drive waits to execute the Run command.
Setting
Description
0
Disabled (factory default)
1
Enabled
Run Command
Output Frequency
Drive Output
Voltage
Interrupted
OFF
ON
Timer Value T
(C1-02)
100 %
0 %
Operat
io
n W
ai
t T
im
e (T
)
Deceleration
Time (C1-02)
Minimum
Baseblock
Time (L2-03)
Minimum
Output
Frequency
100% (Maximum
Output
Frequency)
Output Frequency at Stop Command Input
Ignored
Run Command
Timer Value T
(OPEN)
(CLOSED)
DDLY
Waiting to RUN