C6 carrier frequency, C6-01 normal duty selection, C6-02 carrier frequency selection – Yaskawa iQpump Programming Manual User Manual
Page 34

34
YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
◆
C6 Carrier Frequency
■
C6-01 Normal Duty Selection
Adjustment of parameter C6-01 will affect the Drive’s overload and carrier frequency settings. Generally this parameter does not need
adjustment and should be left at the factory default setting.
■
C6-02 Carrier Frequency Selection
Parameter C6-02 sets the switching frequency of the Drive’s output transistors. It can be changed in order to reduce audible noise and
also reduce leakage current. Cases that may require adjustment to the C6-02 are:
• If the wiring length between the iQpump drive and the motor is long, decrease the carrier frequency
• If speed and torque are inconsistent at low speeds, decrease the carrier frequency
• If leakage current from the iQpump drive is large, decrease the carrier frequency
• If the audible motor noise is too great, increase the carrier frequency (may require iQpump drive current derating)
When parameter C6-02 is set to “0: Low Noise” the iQpump drive uses a carrier frequency of 2 kHz and reduces the motor audible noise
by approximately 5 db. over the conventional 2 kHz setting (C6-02 = 1). The iQpump drive modulates the nominal PWM pattern to
achieve the lower noise. This setting is normally used with high starting torque loads that are frequently started and stopped or,
applications where leakage current needs to be minimized and motor audible noise is important.
Table 2 Carrier Frequency Parameter Factory Defaults (C6-01=2: Normal Duty 2)
Setting
Description
1
Normal Duty 1
2
Normal Duty 2 (factory default)
Setting
Description
0
Low Noise
1
Fc=2.0 kHz
2
Fc=5.0 kHz
3
Fc=8.0 kHz
4
Fc=10.0 kHz
F
Program
*The factory default setting is model dependent
Wiring Length
328 ft or less
Over 328 ft
C6-02 (carrier frequency) setting
1 to 4 (10 kHz max.)
1 to 2 (5 kHz max.)
208 V – 240 V Drives 1
480 V Drives 1
Model
CIMR-P7
C6-02
Carrier
Frequency
(kHz)
C6-03
Carrier
Frequency
Max. (kHz)
C6-04
Carrier
Frequency
Min. (kHz)
C6-05
Carrier
Frequency
Gain
Nominal
HP
Model
CIMR-P7
C6-02
Carrier
Frequency
(kHz)
C6-03
Carrier
Frequency
Max. (kHz)
C6-04
Carrier
Frequency
Min. (kHz)
C6-05
Carrier
Frequency
Gain
Nominal
HP
20P4
4 (10.0)
4 (10.0)
4 (10.0)
0
0.5/0.75
40P4
6 (15.0)
6 (15.0)
6 (15.0)
0
0.5/0.75
20P7
4 (10.0)
4 (10.0)
4 (10.0)
0
1
40P7
6 (15.0)
6 (15.0)
6 (15.0)
0
1
21P5
4 (10.0)
4 (10.0)
4 (10.0)
0
1.5/2
41P5
6 (15.0)
6 (15.0)
6 (15.0)
0
1.5/2
22P2
3 (8.0)
3 (8.0)
3 (8.0)
0
3
42P2
6 (15.0)
6 (15.0)
6 (15.0)
0
3
23P7
4 (10.0)
4 (10.0)
4 (10.0)
0
5
43P7
6 (15.0)
6 (15.0)
6 (15.0)
0
5
25P5
6 (15.0)
6 (15.0)
6 (15.0)
0
7.5
45P5
6 (15.0)
6 (15.0)
6 (15.0)
0
7.5
27P5
6 (15.0)
6 (15.0)
6 (15.0)
0
10
47P5/49P0
6 (15.0)
6 (15.0)
6 (15.0)
0
10/15
2011
3 (8.0)
3 (8.0)
3 (8.0)
0
15
4011
3 (8.0)
3 (8.0)
3 (8.0)
0
15/20
2015
4 (10.0)
4 (10.0)
4 (10.0)
0
20
4015
4 (10.0)
4 (10.0)
4 (10.0)
0
25
2018
4 (10.0)
4 (10.0)
4 (10.0)
0
25
4018/4024
4 (10.0)
4 (10.0)
4 (10.0)
0
30/40
2022
4 (10.0)
4 (10.0)
4 (10.0)
0
30
4030
3 (8.0)
3 (8.0)
3 (8.0)
0
40/50
2030
4 (10.0)
4 (10.0)
4 (10.0)
0
40
4037
3 (8.0)
3 (8.0)
3 (8.0)
0
60
2037
2 (5.0)
2 (5.0)
2 (5.0)
0
50
4045
3 (8.0)
3 (8.0)
3 (8.0)
0
75
2045
2 (5.0)
2 (5.0)
2 (5.0)
0
60
4055
2 (5.0)
2 (5.0)
2 (5.0)
0
100
2055
3 (8.0)
3 (8.0)
3 (8.0)
0
75
4075
2 (5.0)
2 (5.0)
2 (5.0)
0
125
2075
1 (2.0)
1 (2.0)
1 (2.0)
0
75/100
4090
3 (8.0)
3 (8.0)
3 (8.0)
0
150