P2-16 No-Flow Setpoint Compensation

Setting Range:

0.0 to 6000.0

Factory Default: 1.5

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). When the

no-flow detection is activated and the No-Flow Detection Time (P2-13) has elapsed, the system setpoint will be lowered by the value

programmed in the No-Flow Setpoint Compensation (P2-16) for the time programmed in No-Flow Stabilization Time (P2-14).

The No-Flow Setpoint Compensation (P2-16) works in conjunction with the No-Flow Stabilization Time (P2-14). The units for this

parameter are determined by the System Units (P1-02).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-17 No-Flow Feedback Delay Time

Setting Range:

0.0 to 1000.0 sec

Factory Default: 2.0 sec

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). When the

no-flow detection process is activated, and the system setpoint has returned to the original value, the feedback will be monitored. If the

feedback level is within the No-Flow Delta Feedback Level (P2-15), a specific delay time can be programmed in the No-Flow Feedback

Delay Time (P2-17) before the drive enters a “sleep” mode.

The No-Flow Feedback Delay Time (P2-17) works in conjunction with the No-Flow Delta Feedback Level (P2-15).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-18 No-Flow Motor RPM Sample Time

Setting Range:

0.0 to 1000.0 sec

Factory Default: 2.0 sec

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). The no-

flow detection function monitors the motor RPM. The motor RPM monitor sample rate can be programmed in the No-Flow Motor RPM

Sample Time (P2-18).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-19 No-Flow Feedback Detection Direction

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). When the

no-flow detection process is activated, and the system setpoint has returned to the original value, the feedback will be monitored. The

direction of the feedback upon return of the no-flow detection can be selected by programming the No-Flow Feedback Detection

Direction (P2-19).

The No-Flow Feedback Detection Direction (P2-19) works in conjunction with the No-Flow Delta Feedback Level (P2-15).

Refer to the No-Flow Activation Level (P2-11) for further description.

Setting

Description

0

Outside Bandwidth (P2-15) (

factory default)

1

Inside Bandwidth (P2-15)