C2 S-Curve Acc

S-Curve Characteristics

Setting Range:

0.00 to 2.50 sec

Factory Default: 0.20 sec

Parameters C2-01 and C2-02 will affect the acceleration rate of the output frequency in order to reduce shock to the load. The S-curve

addition to the acceleration profile can ramp the acceleration rate from a 0 to the rate specified by the active Acceleration Time (C1-01 or

C1-03) and back to 0.

Figure 1.25

Figure 25 S-curve Characteristic Timing Diagram

The S-Curve transition into and out of the active acceleration rate can be programmed independently. C2-01 will ramp up the

acceleration from no acceleration up to the rate of C1-01 or C1-03. C2-02 will ramp the acceleration rate from the rate of C1-01 or C1-03

back down to no acceleration (constant speed). The use of S-Curve characteristics will lengthen the overall acceleration time as follows:

Figure 1.26

Figure 26 S-Curve Characteristic Timing Diagram