P1-09 High Feedback Level

Setting Range:

0.0 to 6000.0

Factory Default: 155.0 (system units P1-02)

The iQpump drive can be configured to display a High Feedback (HFB) alarm when the feedback level rises above the programmed High

Feedback Level (P1-09). The “HFB” alarm will turn off when the feedback level falls below P1-09 plus the Hysteresis Level (P1-13).

Setting P1-09 to a value of 0 will disable this function. This function is active during operation in the Hand Mode, Auto Mode, Pre-

Charge, and Thrust-Bearing Mode.

The High Feedback Level (P1-09) works in conjunction with High Level Fault Time (P1-10). The units for this parameter are determined

by the System Units (P1-02).

P1-10 High Level Fault Delay Time

Setting Range:

0 to 3600 sec

Factory Default: 2 sec

The iQpump drive can be configured to display a High Feedback (HFB) alarm when the feedback level rises above the programmed High

Feedback Level (P1-09) for the time programmed in the High Level Fault Delay Time (P1-10).

Setting P1-10 to a value of 0 will disable this function.

The High Level Fault Delay Time (P1-10) works in conjunction with High Feedback Level (P1-09).

Note: This function is active during operation in the Hand Mode, Auto Mode, Pre-Charge, and Thrust-Bearing Mode.

P1-11 Maximum Setpoint Difference

<0032>

Setting Range:

0.0 to 6000.0

Factory Default: 0.0 (system units P1-02)

The iQpump drive can be configured to display a Not Maintaining Setpoint (NMS) fault when the difference between the setpoint and the

feedback exceeds the Maximum Setpoint Difference (P1-11). When the Maximum Setpoint Difference has been exceeded, the drive will

trip on NMS fault and will coast to a stop when the fault occurs.

Setting P1-11 to a value of 0 will disable this function. This function is only active during operation in the Auto Mode.

The Maximum Setpoint Difference (P1-11) works in conjunction with the Not Maintaining Setpoint (P1-12). The units for this parameter

are determined by the System Units (P1-02).

Figure 1.97

Figure 102 Not Maintaining Setpoint (NMS) Fault

TIME

Not Maintaining
Setpoint (NMS) Fault

Not Maintaining
Setpoint Time P1-12

P1-11

P1-11

SETPOINT

PRESSURE
FEEDBACK