TM.iQp.02 iQpump Drive Programming Manual
P3-02
0615H
Drive Multi/Maximum
Level
Max-Multi Level
Sets the maximum level used for multiplex pumping operation.
Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01=0:
When the output frequency rises above the level
programmed in P3-02 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-XX = 40, 41).
P3-01=1:
Not Used.
P3-01=2:
When the output frequency rises above level programmed in
P3-02 and the delta feedback (setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure (H2-XX = 40, 41).
0.0 to
120.00
59.0 Hz Programming
P3-03
0616H
Add Pump Delta Level
Add Pump D-Lvl
Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.
P3-01=0:
Not Used.
P3-01=1:
When the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).
P3-01=2:
When the output frequency rises above level programmed in
P3-02 and the delta feedback (Setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure. (H2-XX = 40, 41).
Note:
Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-04
0617H
Add Pump Delay Time
Add Pump Dly Tm
Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
0 to 3600
2 sec
Programming
P3-05
0618H
Shutdown Pump Delta
Level
Shdn Pump D-Lvl
Sets the level used for multiplex pumping operation. Parameter is
active when P3-01 = 1 or P3-01 = 2 is selected.
P3-01=0:
Not Used.
P3-01=1:
When the delta feedback (feedback minus setpoint) has
exceeded the level programmed in P3-05 for a time specified in P3-
06,the last pump that was brought online will be shutdown by means of
a multi-function digital output opening. (H2-XX = 40, 41).
P3-01=2:
When the output frequency drops below level programmed
in P3-09 or P3-10 (depends on last pump running) and the delta
feedback (feedback minus setpoint) has exceeded the level
programmed in P3-05 for a time specified in P3-06, the last pump that
was brought online will be shutdown by means of a multi-function
digital output opening. (H2-XX = 40, 41).
Note:
Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-06
0619H
Shutdown Pump Delay
Time
Shdn Pump Dly Tm
Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.
0 to 3600
5 sec
Programming
P3-07
061AH
Multi Pump Setpoint
Increase
MP Setpoint Inc.
Sets the amount the Drive’s setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Setpoint.
Pump 1+2: Setpoint + P3-07.
Pump 1+2+3: Setpoint + (2 x P3-07).
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
P3-08
061BH
Multi Pump Setpoint
Decrease
MP Setpoint Dec.
Sets the amount the Drive’s setpoint will increase for each time a new
pump is brought online.
Pump 1: Setpoint.
Pump 1+2: Setpoint - P3-08.
Pump 1+2+3: Setpoint - (2 x P3-08).
0.0 to
6000.0
(system
units P1-
02)
0.0
(system
units P1-
02)
Programming
Denotes that parameter can be changed when the Drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.