beautypg.com

Yaskawa iQpump Programming Manual User Manual

Page 127

background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

127

P1-12 Not Maintaining Setpoint and Loss of Prime Time

<0032>

Setting Range:

0 to 3600 sec

Factory Default: 60 sec

The iQpump drive can be configured to display a Not Maintaining Setpoint (P1-11) fault when the difference between the setpoint and

the feedback levels are exceeded for the time programmed in the Not Maintaining Setpoint and Loss of Prime Time (P1-12). The drive

will coast to a stop after the level has been exceeded for the specified time programmed in P1-12.

This function is only active during operation in the Auto Mode.

The Not Maintaining Setpoint and Loss of Prime Time (P1-12) is also used for the Prime Loss Level (P1-14) function. Refer to Prime

Loss Level (P1-14) for further description.

The Not Maintaining Setpoint and Loss of Prime Time (P1-12) works in conjunction with Maximum Setpoint Difference (P1-11) and

Prime Loss Level (P1-14).

Note: The time value programmed into P1-12 is shared by Maximum Setpoint Difference (P1-11) and Prime Loss Level (P1-

14) functions. However, independent times are maintained. If one function time; such as P1-11, has elapsed, the other

functions time (P1-14) is still maintained until this time has elapsed.

P1-13 Hysteresis Level

Setting Range:

0.0 to 100.0

Factory Default: 0.0

The iQpump drive can be configured to detect Low Feedback Level (P1-07) and High Feedback Level (P1-09) alarms. The Hysteresis

Level (P1-13) is used to provide a bandwidth before the drive returns to normal operation. The Hysteresis Level is used to prevent rapid

cycling between alarm and normal operations.

The Hysteresis Level (P1-13) works in conjunction with the Low Feedback Level (P1-07) and High Feedback Level (P1-09) functions.

The units for this parameter are determined by the System Units (P1-02).

P1-14 Prime Loss Level

Setting Range:

0.0 to 1000.0 A

Factory Default: 0.0 A

The iQpump drive can be configured to detect a “loss of prime” in the pump. This drive will display a “LOP” fault when the output

current drops below the Prime Loss Level (P1-14) for the time programmed in the Not Maintaining Setpoint and Loss of Prime Time (P1-

12), and the output frequency is at maximum output frequency. The drive will coast to a stop when a fault occurs.

This function is only active during operation in the Auto Mode.

Note: The Prime Loss Level function is only active when the maximum numbers of pumps defined by P1-01 are running at

maximum frequency.

The Prime Loss Level (P1-14) works in conjunction with Not Maintaining Setpoint and Loss of Prime Time (P1-12).