beautypg.com

Yaskawa iQpump Programming Manual User Manual

Page 164

background image

164

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

P4-03 Pre-Charge Time

Setting Range:

0.0 to 3600.0 min

Factory Default: 0.0 min

The iQpump drive can be configured for a pre-charge function. The maximum allowable time for the pre-charge function is programmed

in the Pre-Charge Time (P4-03). Setting P4-03 to a value of 0 will disable the pre-charge function.

Refer to Pre-Charge Level (P4-01) for further description.

The Pre-Charge Time (P4-03) works in conjunction with the Pre-Change Level (P4-01).

P4-04 Thrust Bearing Acceleration Time

<0032>

Setting Range:

0.0 to 6000.0 sec

Factory Default: 1.0 sec

The iQpump drive can be configured for a thrust bearing function. The acceleration time, when the thrust bearing function is enabled (P4-

05 > 0), is programmed in the Thrust Bearing Acceleration Time (P4-04).

Refer to Thrust Bearing Frequency (P4-05) for further description.

The Thrust Bearing Acceleration Time (P4-04) works in conjunction with the Thrust Bearing Frequency (P4-05).

Figure 1.127

Figure 132

TIME

0 Hz

Thrust Freq.

P4-05

Stop

Auto Mode Run Command

Auto Mode Run

PI Enabled, Continue Normal Auto Operation

Acceleration

Time P4-04

PI Disabled